ĐẦU PHÁT LEROY SOMER LSA 44.3
Leroy somer performance:
Leroy Somer LSA 44.3 single-phase alternator has been designed to offer you the best power generation performances. With its meticulous design and optimized architecture, the single-phase LSA 44.3 strikes the perfect balance between compactness, reliability, performance and longevity.
The single-phase LSA 44.3 alternator is a machine with a dedicated single-phase winding. It has 10 to 40% more power than an equivalent three-phase alternator connected with the same single-phase voltage.
Standards:
Nidec Leroy Somer LSA 44.3 alternator meets all key international standards and regulations, including IEC 60034, NEMA MG 1.32-33, ISO 8528-3, CSA C22.2 n°100-14 and UL 1446 (UL 1004 on request). Also compliant with IEC 61000-6-2,
IEC 61000-6-3, IEC 61000-6-4, VDE 0875G, VDE 0875N and EN 55011, group 1 class A for European zone.
Nidec Leroy Somer LSA 44.3 single-phase alternator can be integrated in EC marked generator set, and bears EC, EAC and CMIM markings. It is designed, manufactured and marketed in an ISO 9001 and ISO 14001 quality assurance environment.
Electrical characteristics and performances:
Class H insulation, 2/3 pitch winding, dedicated single-phase, 4-wire (M or M1) reconnectable (optimized for 240 V / 60 Hz, F. = 1) (15% derating for use at PF = 0.8) (PF = 1 corresponds to general use for single-phase voltage)
Possible voltages:
- 50 Hz: 230 V in series
- 60 Hz: 240 V in series
Excitation and regulation system:
| Excitation system | Regulation options | |||
|
AVR |
SHUNT |
C.T. Current transformer for paralleling |
Mains paralleling |
Remote voltage potentiometer |
| R250 | Standard |
√ |
||
Protection system and options:
The Leroy somer LSA 44.3 is IP 23. Complete winding protection for clean environments with relative humidity ≤ 95%, including indoor marine environments
*Options:
- Filters on air inlet: derating 5%
- Filters on air inlet and air outlet (IP 44): derating 10%
- Reinforced winding protection for harsh environments and relative humidity greater than 95%
- Space heater
- Thermal protection for stator windings
- Shaft height: H = 225 mm (to be specified when ordering)
Mechanical construction:
- Compact rigid assembly to better withstand generator vibrations
- Steel frame and terminal box
- Aluminum flanges and shields
- Two-bearing and single-bearing versions designed to be suitable for commercially-available heat engines
- Half-key balancing two-bearing
- Greased for life bearings (20 000h)
- Direction of rotation: clockwise and anti-clockwise (without derating)
Terminal box design:
- Easy access to the voltage regulator (lid) and to the connections
- 4-way terminal block for reconnecting the voltage
- Predrilled holes for cable gland
General characteristics:
| Insulation class | H | Excitation system | SHUNT | |
| Winding pitch | 2/3 (wind. M 50 Hz, M1 60 Hz) | AVR type | R 250 | |
| Number of wires | 4 | Voltage regulation (*) | ± 0.5 % | |
| Protection | IP 23 | Short-circuit current | – | |
| Altitude | ≤ 1000 m | Total Harmonic Distortion THD (**) in no-load < 3 % | ||
| Overspeed | 2250 R.P.M. | Total Harmonic Distortion THD (**) on linear load < 5 % | ||
| Air flow | 0.25 m3/s (50 Hz) / 0.30 m3/s (60 Hz) | Waveform: NEMA = TIF (**) < 50 | ||
| (**) Total harmonic distortion between phases, no-load or on-load (non-distorting) | ||||
*High performance and reliable industrial alternator for all types of generator sets
| Power | 70 – 200 kVA* |
| Voltage | 220 – 440V |
| Poles | 4 |
| Speed | 1500 – 1800 rpm |
| Shaft height | 270 mm |
| Max efficiency | 95.6 % |
| Excitation | SHUNT / AREP / PMG |
| Regulation | R250 / D350 / D550 |
* kVA/50Hz – kW/60Hz | Continuous / 40°C (Discrepancies may occur, consult catalogue for exact figures)
Key features:
| Insulation class | H |
| Winding pitch | 2/3 (wdg 6) |
| Number of wires | 12 |
| Protection | IP 23 |
| Altitude | ≤ 1000 m |
| Overspeed | 2250 rpm |
| Air flow | 0.25m3/s, 50 Hz -0.3m3/s, 60 Hz |
| Excitation system / AVR type | SHUNT / R250 – AREP / D350 |
| Voltage regulation (Steady state) | ±0.5% SHUNT / ±0.25% AREP |
| Short-circuit current (3 IN / 10 s) | 300 % (3 IN) : 10s |
Regulation:
| Regulators | R250 | D350 | D550 |
| Mains Paralleling | – | – | ● |
| 3-phase sensing | – | ● | ● |
| Advanced settings | – | ● | ● |
| Data logging & monitoring | – | ● | ● |
| Remote communication | – | ● | ● |
| Remote voltage potentiometer | – | ○ | ○ |
| CT for mains paralleling | – | ○ | ○ |
| R791 RFI suppression kit (standard in Europe) | ○ | ○ | ○ |
● : Included ○ : Option – : Not available
Coupling:
| Flex plate / Flange | 1 | 2 | 3 | 4 |
| 14 | ● | – | – | – |
| 11 1/2 | ● | ● | ● | – |
| 10 | ● | ● | ● | ● |
| 8 | – | – | ● | ● |